Figure CFD2-8: Comparison of 3D simulation results (U/Uo and k/Uo2) with experimental data (See [http://qnetkb.cfms.org.uk/TA4/AC4-01/I/CFD2-8.jpg CFD2-8.jpg] for an enlarged view of the figure above)
Figure CFD2-8: Comparison of 3D simulation results (U/Uo and k/Uo2) with experimental data
(See [[Media:AC4-01_CFD2-8.jpg|CFD2-8.jpg]] for an enlarged view of the figure above)




Line 195: Line 196:
The comparison of U and k profiles at the runway location, normalised by the free-stream velocity U0,is shown in Figure CFD2-10. The mean velocity profiles simulated with and without the building are virtually identical, suggesting that the building had no effect on the mean velocity profile at the location of the runway. The comparison of the k profiles at the runway location shows that the simulation under-predicts the turbulence levels in the building wake. However, as with the 3D simulations, the 2D simulation overpredicts the increase in turbulence ([[DOAP]]2), by a factor of 2. Therefore, the reason for the lower overall turbulence levels is due to much lower levels of turbulence in the incident wind profile prescribed at the inlet (BL2) compared to the experimental profile.
The comparison of U and k profiles at the runway location, normalised by the free-stream velocity U0,is shown in Figure CFD2-10. The mean velocity profiles simulated with and without the building are virtually identical, suggesting that the building had no effect on the mean velocity profile at the location of the runway. The comparison of the k profiles at the runway location shows that the simulation under-predicts the turbulence levels in the building wake. However, as with the 3D simulations, the 2D simulation overpredicts the increase in turbulence ([[DOAP]]2), by a factor of 2. Therefore, the reason for the lower overall turbulence levels is due to much lower levels of turbulence in the incident wind profile prescribed at the inlet (BL2) compared to the experimental profile.


Velocity profiles from the 2D solution were examined at locations between the building and the runway. Though a noticeable velocity deficit did occur in the wake of the building, the mean velocity had ‘recovered’ before reaching the runway, at about ~14H. This premature recovery is clearly contrary to results from other experimental studies. A study by Castro ([Ref. CFD2-5], see also [http://qnet.cfms.org.uk/data/TA4/AC4-01/UFR3-14 UFR3-14]) of the wake effects of a 3D bluff body immersed in a 2D boundary layer suggest that for a body of similar size, recovery of the mean velocity profile should be expected after a distance of ~50H downstream.
Velocity profiles from the 2D solution were examined at locations between the building and the runway. Though a noticeable velocity deficit did occur in the wake of the building, the mean velocity had ‘recovered’ before reaching the runway, at about ~14H. This premature recovery is clearly contrary to results from other experimental studies. A study by Castro ([Ref. CFD2-5], see also [[UFR_3-14#|UFR3-14]]) of the wake effects of a 3D bluff body immersed in a 2D boundary layer suggest that for a body of similar size, recovery of the mean velocity profile should be expected after a distance of ~50H downstream.


The point at which the flow reattaches on the ground downstream of the building was also estimated by inspection of the streamline diagrams (Figure CFD2-11). This was found to be equal to 3H, which is too short compared to Castro’s data for a bluff body submersed in a boundary layer. Again, the over-prediction of turbulence by the k-ε model is probably the cause of this premature re-attachment. As unphysically high levels of turbulence are transported downstream, they are thought to cause an increase in the mean velocity as momentum is transferred from high k areas to parts of the boundary layer that have been retarded by the building.
The point at which the flow reattaches on the ground downstream of the building was also estimated by inspection of the streamline diagrams (Figure CFD2-11). This was found to be equal to 3H, which is too short compared to Castro’s data for a bluff body submersed in a boundary layer. Again, the over-prediction of turbulence by the k-ε model is probably the cause of this premature re-attachment. As unphysically high levels of turbulence are transported downstream, they are thought to cause an increase in the mean velocity as momentum is transferred from high k areas to parts of the boundary layer that have been retarded by the building.
Line 206: Line 207:




Figure CFD2-10: Comparison of 2D simulation results (<math>U/U_{o}</math> and <math>k/U_{o2}</math>) with experimental data (See [http://qnetkb.cfms.org.uk/TA4/AC4-01/I/CFD2-10.jpg CFD2-10.jpg] for an enlarged view of the figure above)
Figure CFD2-10: Comparison of 2D simulation results (<math>U/U_{o}</math> and <math>k/U_{o2}</math>) with experimental data (See [[Media:AC4-01_CFD2-10.jpg|CFD2-10.jpg]] for an enlarged view of the figure above)





Latest revision as of 16:35, 11 February 2017

Front Page

Description

Test Data

CFD Simulations

Evaluation

Best Practice Advice

Wind environment around an airport terminal building

Application Challenge 4-01 © copyright ERCOFTAC 2004


Overview of CFD Simulations

CFD calculations were carried out by the University of Southampton [CFD2] to calculate the flow and turbulence in the wake of the terminal building at various points over the adjoining runway.

Simulations at the University of Southampton were carried out by James Forrest [Ref. 6], with the commercial code FLUENT using the standard k-ε turbulence model. Preliminary simulations of the boundary layer flow in the empty tunnel formed the basis for 2D and 3D calculations for main terminal building, using a simplified representation of its geometry and omitting surrounding buildings.


Table CFD-A Summary Description of all Test Cases
NAME GNDPs PDPs (problem definition parameters) SPs (simulated parameters)
Re (full scale) Wind direction detailed data DOAPs
CFD 2 2D and 3D runaway wind environments simulations (plus empty tunnel simulations) ~5x106 180 Ux, Uy, Uz, k Mean velocity, turbulence kinetic energy profiles

References

[Ref. 6] Forrest J. (2003) CFD for the airflow around an airport terminal building, MEng project report, University of Southampton.



Simulation Case CFD2

Solution strategy

The commercially available CFD code FLUENT (version 5) was used [Ref. CFD2-1]. The incompressible, isothermal RANS equations were solved, using the standard k-ε turbulence model with standard constants, and standard wall functions The numerical discretisation scheme used was second-order. The default pressure-velocity coupling algorithm SIMPLE, and the ‘segregated’ solver option, were employed.


Computational Domain

Three meshes were constructed: an empty tunnel box in 2D to simulate the empty tunnel, and two models of the main terminal building, in 3D and 2D. The geometry of the terminal building was simplified to the 2D shape shown in Figure CFD2-1, and this profile was extruded to create the 3D shape. The terminal building was modeled in isolation; neighbouring buildings were not included to simplify the CFD mesh. This omission will affect the flow locally, and since the neighbouring buildings are situated upstream of the terminal building and their heights are relatively low compared to the main building (~0.3H), it anticipated that the overall shape and dimensions of the wake will be primarily influenced by the geometry of the terminal building rather than that of the neighbouring buildings. As a result, the DOAPs for this Application Challenge, i.e. the velocity defect and turbulence intensity at the runway will probably be unaffected.


Image373.gif


Figure CFD2-1: Simplified 2D profile for the main terminal building


Empty tunnel 2D mesh: A regular hexahedral 2D mesh was created, to simulate the flow in the empty tunnel, as illustrated in Figure CFD2-2 The first vertical node was placed at z/δ=0.0229 and a further 34 nodes placed according to a logarithmic profile so that the spacing between the topmost node and the top of the domain was z/δ=0.086.


Image374.gif


Figure CFD2-2: 2D empty tunnel mesh


3D mesh: Only half of the building was modeled, placing a symmetry boundary along the y-z plane at half the building length (as illustrated in Figure CFD2-3).

The computational domain around the building was a rectangular box which extended 20H upstream of the building, 50H downstream, and 10H above. This is much more extensive than the recommendation by Cowan et al. [Ref. CFD2-2] that the computational domain around a building should not be smaller than 5H upstream and 15H downstream, since the runway was positioned 14H downstream of the building and therefore had to be kept sufficiently away from the outlet. Increased refinement was used in a region 3H high and 7H long around the building, where a grid spacing of Δm=0.5m=1.4%H was used. This was chosen to fulfill the criterion of 1%H recommended by Castro et al. [Ref. CFD2-3] to fully resolve the shear layer in separated flows. Elsewhere in the domain a gradual expansion ratio (less than 1.2) was used. Additional embedded refinement was also used to refine the mesh around the leading edge of the roof and the raised section, as illustrated in Figure CFD2-5. A cross-streamwise width of 8H was used; Cowan et al. [Ref. CFD2-3] recommended that this should not be smaller than 4H. The mesh consisted of tetrahedral cells around the building, but further from the building a Cartesian grid was used, as illustrated in Figure CFD2-4. The total number of cells was ~2x106.


Image375.gif


Figure CFD2-3: The extruded 3D building geometry (mirrored at the line of symmetry)


Image376.gif


Figure CFD2-4: Detail of the mesh discretisation around the 3D building geometry


Image377.gif


Figure CFD2-5: Local refinement around the leading edge of the roof and the raised section


2D mesh: In addition to the 3D mesh, a 2D mesh of similar domain size and mesh refinement was created, to illustrate the differences between a 2D and 3D solution. Tetrahedral cells were used throughout and the total number of cells was ~90,000.

Boundary Conditions

The zero gradient condition was specified at the outlet, and symmetry boundaries were specified at the top and sides of the domain. The position of the inlet and outlet boundaries was placed at a distance well away from the building and the measurement location, as discussed in the previous section. The wall surfaces were modeled using wall functions; the ground plane was modeled as a rough wall, the aerodynamic roughness matching that simulated in the wind tunnel, and using a smooth wall roughness for the building walls.

Much effort was invested in defining appropriate inlet conditions, i.e. appropriate vertical profiles of velocity, k and ε. Although it was possible to replicate the mean velocity profile measured in the wind tunnel, the CFD profiles for k underestimated the measured values.

The following two approaches were considered:

BL1: profiles of U, k and ε were taken from a distance of 25H downstream of the inflow boundary. These were used as inlet boundary conditions for another flow computation. A modified value of Cμ=0.0163 was used to match the wind tunnel value of k at the wall based on:



Other constants , and were left unchanged. Once the solution had converged, profiles of U and k were examined at various locations, and were found to remain constant along the domain.

BL2: the established method of Castro and Apsley [Ref. CFD2-4] was used whereby:



and



using the default value of .

In FLUENT [Ref. CFD2-1] the roughness of the wall is specified via a wall roughness height, Ks, and a roughness constant, CKs, rather than the aerodynamic roughness z0, though these are roughly related via the expression:



where is an empirical constant set to 9.81. An appropriate range of values for CKs =0.5 to 1, and CKs=1 was chosen, and Ks was set to give a value of z0 which most closely matched the experimental data.

Profiles BL1 and BL2 are plotted in Figure CFD2-6, compared against experimental values. The velocity profile for BL2 matched the experimental one closely, but the k-profile values are much lower than the experimental ones. The velocity profile for BL1 departs slightly from the experimental one, and though the k values are larger than those obtained with BL1 and are correct at the wall, the profile is still significantly different to that measured. Possible reasons for the discrepancy could be a deficiency in the k-ε model, the need to modify constants other than Cμ. However, it is also possible that the boundary layer created in the wind tunnel was still developing and had not reached equilibrium, i.e. the wind tunnel boundary layer conditions were inappropriate for the purposes of this study.


Image378.gif


Figure CFD2-6: Comparison of mean velocity profiles for simulated boundary layers BL1 and BL2.


Image379.gif


Figure CFD2-7: Comparison of k profiles for simulated boundary layers BL1 and BL2.


Application of Physical Models

Standard wall functions were applied at wall surfaces, as described in ‘Boundary Condition’ above. Details of the mesh distribution near the walls and y+ values were not reported.


Numerical Accuracy

The convergence criterion used was reducing scaled residuals to below 10-5, and this was achieved for both the 2D and 3D simulations. This level of convergence (which is well below the default 10-3 value used in FLUENT) was deemed necessary to obtain results that were numerically accurate; during preliminary simulations of the boundary layer evolution in the empty tunnel geometry it was found that the boundary layer shape near the outlets was distorted when residuals were greater than 10-4.


CFD Results

The mean velocity and turbulence kinetic energy profiles, with and without the buildings, are used to compare and evaluate the CFD results. These are presented in graphical format only; no datafiles are provided.

3D simulations:

The comparison of U and k profiles at the runway location, normalised by the free-stream velocity U0,is shown in Figure CFD2-8. Note that this normalisation is different to that used to non-dimensionalise the experimental values (relative to ‘empty tunnel’ data).

The mean velocity profile agrees well with experimental data (within 5-10%). The k profile is in partial agreement with the data, and the k peak occurs at a lower value than the tunnel data. The simulated and experimental maximum values of k/Uo2 are similar, but this agreement is most probably coincidental and the result of the much lower levels of turbulence prescribed at the inlet balancing the over-generation of turbulence around the building. The numerical model predicts a 400% increase in k compared to the empty tunnel case, which is well above the 50-60% increase in the experimental data. Thus, the increase in turbulence (DOAP2) is over-predicted by a factor of 5.

The inadequacies of the k-ε turbulence model with regards to excessive k production are well-documented and could be the reason underlying the excessive turbulence production. In areas of high streamwise strain rates which occur around bluff bodies the k-ε model is known to fail to model the turbulence dissipation adequately and therefore over-predicts the turbulence kinetic energy in those areas. Figure CFD2-9 illustrates the areas in the solution where the turbulence energy is created, namely upstream of the leading edges of the roof and around the raised section.


Image380.gif

Figure CFD2-8: Comparison of 3D simulation results (U/Uo and k/Uo2) with experimental data (See CFD2-8.jpg for an enlarged view of the figure above)


Image381.gif


Figure CFD2-9: Turbulence energy isosurface for k/U0=0.33.


2D simulations: these were preliminary simulations preceding the 3D simulations. They were initially run using the BL1 inlet conditions but the solution gave physically unrealistic results and subsequently diverged. For this reason, the use of BL1 was abandoned and all subsequent simulations in 2D and 3D were carried out using BL2.

The comparison of U and k profiles at the runway location, normalised by the free-stream velocity U0,is shown in Figure CFD2-10. The mean velocity profiles simulated with and without the building are virtually identical, suggesting that the building had no effect on the mean velocity profile at the location of the runway. The comparison of the k profiles at the runway location shows that the simulation under-predicts the turbulence levels in the building wake. However, as with the 3D simulations, the 2D simulation overpredicts the increase in turbulence (DOAP2), by a factor of 2. Therefore, the reason for the lower overall turbulence levels is due to much lower levels of turbulence in the incident wind profile prescribed at the inlet (BL2) compared to the experimental profile.

Velocity profiles from the 2D solution were examined at locations between the building and the runway. Though a noticeable velocity deficit did occur in the wake of the building, the mean velocity had ‘recovered’ before reaching the runway, at about ~14H. This premature recovery is clearly contrary to results from other experimental studies. A study by Castro ([Ref. CFD2-5], see also UFR3-14) of the wake effects of a 3D bluff body immersed in a 2D boundary layer suggest that for a body of similar size, recovery of the mean velocity profile should be expected after a distance of ~50H downstream.

The point at which the flow reattaches on the ground downstream of the building was also estimated by inspection of the streamline diagrams (Figure CFD2-11). This was found to be equal to 3H, which is too short compared to Castro’s data for a bluff body submersed in a boundary layer. Again, the over-prediction of turbulence by the k-ε model is probably the cause of this premature re-attachment. As unphysically high levels of turbulence are transported downstream, they are thought to cause an increase in the mean velocity as momentum is transferred from high k areas to parts of the boundary layer that have been retarded by the building.

It is therefore clear that, in contrast to the 3D simulation, the 2D simulation predicts recovery of the mean velocity profile at a much shorter distance downstream of the building, thus failing to predict the velocity defect at the runway (DOAP1).


Image382.gif


Figure CFD2-10: Comparison of 2D simulation results ( and ) with experimental data (See CFD2-10.jpg for an enlarged view of the figure above)


Image383.gif


Figure CFD2-11: 2D simulation – velocity vector diagram for 2D flow around the terminal building

References

[Ref. CFD2-1] FLUENT Users’ Guide July 1998, Fluent Inc.

[Ref. CFD2-2] Cowan I. R., Castro I. P., Apsley D. D. (1997) “Numerical considerations for simulations of flow and dispersion around buildings” Journal of Wind Engineering and Industrial aerodynamics, Vol. 67&68, pp. 535-545.

[Ref. CFD2-3] Castro I. P. Cowan I. R. and Robins A.G. (1999) “ Simulations of flow and dispersion around buildings” Journal of Aerospace Engineering, pp. 145-160.

[Ref. CFD2-4] Castro I. P. and Apsley D. D. (1997) Flow and dispersion over topography: a comparison between numerical and laboratory data for two dimensional flows” Atmospheric Environment, Vol. 31, No. 6, pp. 839-850

[Ref. CFD2-5] Castro I. P. (1979) “Relaxing wakes behind surface-mounted obstacles in rough wall boundary layers” Journal of Fluid Mechanics, Vol. 93, Part 4, pp.631-659.